INC-2041
14:22 local
BMS · Niagara
High
CRAH-2B supply air temperature high
Data Hall 2 · Asset CRAH-2B · Setpoint 18.0°C
Observed
- Supply air 27.4°C and rising about 0.4°C per minute.
- Filter differential pressure 248 Pa on CRAH-2B. Baseline for this unit is 110 Pa.
- WO-1184 closed six hours ago on adjacent CRAH-2A, belt inspection. This unit was not in that job.
Agent analysis
Likely restricted airflow from a loaded filter on CRAH-2B.
Supply temperature is climbing while filter ΔP is more than double baseline. The neighboring CRAH was just worked; CRAH-2B’s last filter record is outside the SOP interval. Chilled-water valve position is already near full open, so the coil is not the first explanation.
SOP-CRAH-FLT-04 · filter ΔP above 200 Pa
No isolation is recommended until an operator accepts the work order.